Movincool Office Pro 60 Manuale di Servizio

Navigare online o scaricare Manuale di Servizio per Climatizzatori a split Movincool Office Pro 60. Movincool Office Pro 60 Service manual [en] Manuale Utente

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa

Sommario

Pagina 1 - SERVICE MANUAL

SERVICE MANUALOFFICE PRO 12

Pagina 2

CONSTRUCTION AND SPECIFICATIONS6EXHAUST AIR VENTCOOL AIR VENTEVAPORATORCAPILLARY TUBEDRAIN TANKDRAIN SWITCHCONTROL BOXCOMPRESSORCONDENSERCENTRIFUGAL F

Pagina 3 - DEFINITION OF TERMS

CONSTRUCTION AND SPECIFICATIONS7ACCUMULATORCONDENSER FANFAN MOTORSIDE PANELRIGHT HANDLEEXHAUST AIR VENTCONDENSERPOWER CORDCAPILLARY TUBECOMPRESSORDRAI

Pagina 4

CONSTRUCTION AND SPECIFICATIONS8@ 115V40 50 60 70Relative Humidity of Inlet Air (%)6 (10.8)8 (14.4)10 (18.0)12 (21.6)14 (25.2)Temperature ˚C (˚F)Cool

Pagina 5 - GENERAL DESCRIPTION

REFRIGERANT SYSTEM9REFRIGERANTFLOWCOMPRESSORACCUMULATOREVAPORATORFANMOTORCONDENSERCAPILLARYTUBECOMPRESSORACCUMULATOREVAPORATORCONDENSERCAPILLARYTUBERe

Pagina 6

REFRIGERANT SYSTEM10Compressor Operation2.CompressorThe compressor used for the unit is hermeticallysealed. The compressor and the compressormotor ar

Pagina 7

REFRIGERANT SYSTEM11High Temp. / High Press.Liquid RefrigerantLow Temp. / Low Press.Gas and Liquid MixtureFrom EvaporatorTo CompressorCapillary TubeAc

Pagina 8

REFRIGERANT SYSTEM12EVAPORATORINLET PIPEEVAPORATOROUTLET PIPEASSYCAPILLARY TUBECONNECTING PIPE(Evaporator to Compressor)CONNECTING TUBE(Condenser to C

Pagina 9 - 165 (75)

ELECTRICAL SYSTEM13GAPGSCPTBT R R1 R2CC12G120LCL0HIGCF12MCJ4J5J6J2J1J3J8 (AUX1)RB CBTHS RTH DS321AUX2MFIOLFAP Attachment PlugTB Terminal BlockCB Contr

Pagina 10 - Construction of Office Pro 12

ELECTRICAL SYSTEM141.Basic Operation Of the Office Pro 12 Electrical CircuitThere are two basic components used to control the operation of the Office

Pagina 11 - Construction Diagram

ELECTRICAL SYSTEM15CompressorCapacitorFan Motor CapacitorTerminal BlockRelay BoardRelay Board FuseDIP SwitchRelay Board FuseS1CFSTOP OPERATEJ9Temperat

Pagina 12 - Cooling Capability Curve

© 1998 DENSO SALES CALIFORNIA, INC.All rights reserved. This book may not be reproduced or copied, in whole or in part, withoutthe written permission

Pagina 13 - REFRIGERANT SYSTEM

ELECTRICAL SYSTEM16CF1 (White)CF2 (Brown/White)J5 Low (Red)J6 High (Black)Ground(Green/Yellow)Fan Motor3.Fan MotorThe fan motor is a single phase, ind

Pagina 14

ELECTRICAL SYSTEM172NCC1DS2DS1To J103DRAINSWITCHDRAIN WDRAIN WATERTERBASEPLATEBASESPRINGDRAIN TUBEEVAPORATORDRAIN TANKFULCRUMDRAIN PANTOP OFBASEPLATEO

Pagina 15

ELECTRICAL SYSTEM1810.Compressor ProtectionThere is a Time Delay program within the microprocessor. This prevents a heavy load from being appliedon t

Pagina 16

TROUBLESHOOTING AND REPAIR19Before troubleshooting the system, the following inspection should be performed.1.Inspection of Power Source VoltageCheck

Pagina 17 - ELECTRICAL SYSTEM

TROUBLESHOOTING AND REPAIR20COOLAIR OUTTHERMOMETEREVAPORATORAIR INTHERMOMETERSpine FinsOperating EnvironmentCooling CapacityIn case of trouble, perfor

Pagina 18

TROUBLESHOOTING AND REPAIR21Top Front PanelAir Outlet GrilleFront Panel Filter AssyLeft HandleRoom ThermistorDrain Pan AssyFreeze Thermistor7Service P

Pagina 19

TROUBLESHOOTING AND REPAIR22222A. Remove drain tank.B. Remove six (6) screws from upper frontpanel.C. Slide upper front panel forward and remove.Remov

Pagina 20

TROUBLESHOOTING AND REPAIR23DISCONNECTDISCONNECTDISCONNECTRemoval of Power Cord Screws4D. Louver can be removed from upper frontpanel by unsnapping it

Pagina 21

TROUBLESHOOTING AND REPAIR243334Removal of Back and Upper Rear panel ScrewsRemoval of Electrical Parts in the Control BoxG. Remove thirteen (13) screw

Pagina 22

TROUBLESHOOTING AND REPAIR25S1CFSTOP OPERATEJ9J8J4J1J5J2J6J3F1Main Wiring HarnessRelay Board to Control PanelTemperature Scale Display SwitchßC

Pagina 23 - TROUBLESHOOTING AND REPAIR

iFOREWORDThis manual has been published to service the MovinCool Office Pro 12. Please use this service manual onlywhen servicing the Office Pro 12.D

Pagina 24

TROUBLESHOOTING AND REPAIR26Evaporator Fan CasingEvaporator FanFan MotorCondenser FanCasing AssyCondenser FanRing Sub-AssyMotor StayMiddle Frame Sub-A

Pagina 25

TROUBLESHOOTING AND REPAIR27Removal of Centrifugal FanRemoval of Blower HousingRemoval of Fan MotorRemoval of BlowerA. Loosen the set screw using an a

Pagina 26

TROUBLESHOOTING AND REPAIR28331313Removal of Screws for Left Side PanelRemoval of Screws for Right Side PanelRemoval of Control PanelRemoval of Contro

Pagina 27

TROUBLESHOOTING AND REPAIR29Removal of Connectors from Control PanelRemoval of Control BoardI. Disconnect the following connectors from thecontrol boa

Pagina 28

TROUBLESHOOTING AND REPAIR302NCC1DS2DS1To J103DRAINSWITCHTOP OFBASEPLATEInspection of Drain SwitchInspection of Fan Motor13. Inspection of Drain Switc

Pagina 29

TROUBLESHOOTING AND REPAIR3116. Inspection of Wiring ConnectionRefer to the Wiring Diagrams on page 39 and check for connection of each wire.17. Inspe

Pagina 30

TROUBLESHOOTING AND REPAIR3219. Repair of Refrigerant SystemIn case there is a leak, obstruction, or trouble in the refrigerant system of the Spot Coo

Pagina 31

TROUBLESHOOTING AND REPAIR33FDGEBACPART TO REPLACE DISCONNECT ATCompressor A & BCondenser A & CCapillary Tube D, E, & GEvaporator E &

Pagina 32

TROUBLESHOOTING AND REPAIR3420. Charging the System with R-22 RefrigerantAlways ensure that the refrigerant system has been properly evacuated before

Pagina 33

TROUBLESHOOTING AND REPAIR35B. Evacuation(1) Open the high pressure valve (HI) and thelow pressure valve (LO) of the gaugemanifold.(2) Turn on the vac

Pagina 35

TROUBLESHOOTING AND REPAIR36(2)Loosen the nut on the gauge manifoldside of the charging hose (green).(3)Open the high pressure valve of thegauge manif

Pagina 36

TROUBLESHOOTING AND REPAIR37(3) Securely place the refrigerant cylinder ona scale with a weighing capacity of 70 lbs(30 kg) that is graduated by 0.2 o

Pagina 37

TROUBLESHOOTING AND REPAIR38Reassemble the unit in the reverse order of removal.Described below are the parts that require specialcare in reassembling

Pagina 38

TROUBLESHOOTING AND REPAIR39GAPGSCPTBT R R1 R2CC12G120LCL0HIGCF12MCJ4J5J6J2J1J3J8 (AUX1)RB CBTHS RTH DS321AUX2MFIOLFAP Attachment PlugTB Terminal Bloc

Pagina 39

NOTES40

Pagina 40

DENSO SALES CALIFORNIA, INC.TECHNICAL SERVICE DEPARTMENTSecond Issue: November 1998First Issue: October 1998DSCA P/N: LA990009-0435Printed in USA

Pagina 41

DSCA P/N: LA990009-0435

Pagina 42

GENERAL DESCRIPTION1CONDENSER(OUTDOOR UNIT)EVAPORATOR(INDOOR UNIT)Conventional Air ConditionerOffice Pro 12Generally speaking conventional air conditi

Pagina 43

GENERAL DESCRIPTION2

Pagina 44

CONSTRUCTION AND SPECIFICATIONS3ø11.57520.6727.402.204.6012.4043.903.8018.5011.30 7.50 21.202.4016.5019.30Exterior Dimensions (units: inches)

Pagina 45

CONSTRUCTION AND SPECIFICATIONS41.Basic ConstructionThe MovinCool Spot Cooling System is compactin construction because the condenser and theevaporato

Pagina 46 - DSCA P/N: LA990009-0435

CONSTRUCTION AND SPECIFICATIONS5Specifications Specifications are subject to change without notice.Rating Conditionsdry bulb .......