Operation Section
25
6.6 Condensate Pump
The Office Pro 60 is equipped with a condensate pump, which collects the water that forms on
the evaporator during normal cooling operation and eliminates the need for a drain tanks.
- When the water collects to level (A) in the
pump reservoir, the condensate pump begins
to operate and discharge the water. During
condensate pump operating period the
compressor cycles off.
- When the water level drops below level (B),
the condensate pump stops and compressor
restarts after delay time has expired.
< NOTE >
If for any reason the water level exceeds that of level (A) in the pump reservoir, an overflow drain
switch stops the compressor operation.
If the fan mode control DIP switch has been set from the cool to the stop position, the fan also
turns off while the condensate pump is discharging the water.
I001918
Cover
Motor Fan
Mounting Ear
Main Control Float
Reservoir
3/8 in (9.53 mm) I.D.
Drain Outlet Spout
with Check Valve
1 in (25.4 mm)
Inlet Drain Hole
I001919
A
B